D.O.L. STARTER TO MOTOR MATRIX – 3phase
Motor size_____________Overload size___________D.O.L. Size
0.37kW________________0.6-1.0A_________________4-6A
0.55kW________________1.0-1.6A_________________4-6A
0.75kW________________1.6-2.5A_________________4-6A
1.10kW________________1.6-2.5A_________________4-6A
1.50kW________________2.5-4.0A_________________4-6A
2.20kW________________4.0-6.0A_________________4-6A
3.00kW________________5.5-8.0A_________________4-6A
4.00kW________________7.0-10A___________________9A
5.50kW________________9.0-13A__________________12A
7.50kW________________12-18A___________________18A
11.00kW________________17-25A___________________25A
15.00kW________________23-32A___________________32A
18.50Kw________________23-32A___________________40A