A point of note, this compressor is rated as a 1/4 hp Domestic compressor,
If you are really in the need and cannot get a correct replacement
compressor, the also check out the specs on a 1/3 HP Domestic
Compressor. The 1/3 hp Compressor is about 12 % bigger than a 1/4 HP compressor and many times the Condenser is slightly overrated and can accept this compressor
Click Here to make sure you have chosen the correct Compressor
How to Test A Domestic Single
phase (220 Volt) Refrigeration Compressor
Some Basics First
These Refrigeration Compressor have a Starting Capacitor
(Normally between 60 and 80 uf (Micro-farads )
Unplug the refrigerator or turn off the breaker that powers
it. Since you will have to get to the inside of the condenser unit
of the refrigerator anyway, I would recommend you unplug it
On the side of the condenser unit you should see the
terminal box with wires coming out of it. Remove the cover from this
box. The cover will be held in place by either screws or retaining
clips.
With the cover off, you should see the Start relay, and one
or two Capacitors, one WILL be about 60 to 80 uf this
is the Start Capacitor
If there is another Capacitor it will be in the range of 10
to 30 uf this is a Running Capacitor and has
little to do with Stating the Compressor
There are a number of tests that
you can perform to check if the Refrigeration compressor in faulty
Examine the Connections especially on
the Compressor
The Smaller commercial compressor have
their Starting relays on the compressor with the Start Capacitor
outside the terminal box, proceed to do the normal checks on the
Start and Clixton /Overload relay
Use the long-nose pliers to pull the wire connector off of
the relay. Pull it off by gripping the connector, NOT the wire.
Inspect both the connector and the relay for any signs of corrosion.
If there are any, then you should replace the part.
Use the long-nose pliers to pull the wire connector off of
the relay. Pull it off by gripping the connector, NOT the wire.
Inspect both the connector and the relay for any signs of corrosion
or heat damage. If there are any, then you should replace.
The bigger units have a starter box
housing the Start Relay, and terminals for the condenser fan and
Pressure switch
Test the Start Capacitor.
Be Very Careful here you are
working With Voltage and Capacitance you are in danger of Electrical
shock if you are negligent
If you have a megger, Set it to 500
Volts
See if the Capacitor can hold a
charge , wait a short while then short the terminals out , The
Capacitor should Discharge in a reasonably load bang and Flash if
the capacitor is healthy
A health Capacitor will charge and
slowly indicate on the megger that the capacitor is Zero conductive
at empty and Moves to infinite conductivity as the capacitor becomes
charged
If the refrigeration compressor
Fails to start up due to a short term mechanical error try
increasing the valve of your micro-farads of the start compressor
say to 100 or 120uf, this bang is normally adequate to get the a
healthy but impaired compressor going again.
Test the RUN Capacitor
If you have a megger, Set it to 500
Volts
See if the Capacitor can hold a
charge , wait a short while then short the terminals out , The
Capacitor should Discharge with a lesser load bang and Flash if the
capacitor is healthy. Remember that the run capacitor is a much
smaller Capacitor than the Start Capacitor
A health Capacitor will charge and
slowly indicate on the megger that the capacitor is Zero conductive
at empty and Moves to infinite conductivity as the capacitor becomes
charged
A faulty Run capacitor shows
itself in the compressor drawing to many amps ( current to high) or
a healthy compressor stalling for no reason
Winding Burnt to earth
Set your Multimeter to Max Ohms reading(You know, the one
that wants to read if you just touch the Probe terminals) or Meggar
to 500v .Touch one of the tester's probes to Earth or a copper pipe
and leave it there. (Test the meter to make sure its set correctly)
Then, use the other probe to touch first one then the other
terminals and finally the last one.
The tester should display a reading of "zero" ohms
or Clear reading for each test. The compressor is in Order
Any reading here indicates that the wiring is no longer
insulated and touching earth. The compressor has to be failed
Winding Burnt Between Coils / Windings
On the Compressor you will see three terminal points randomly
number them a,b,c or 1,2,3, or left, right, top, Whatever......
Set your Multimeter to read Ohms reading or set your Meggar
to Ohms . (Test the meter to make sure its set correctly) Then, Set
one probe to touch first one “a” or “1” or whatever Now
leaving this probe on this terminal take the other probe and Test:
Ohm reading “a” to “b” = record reading a-b
Ohm Reading “a” to “c” = record reading a-c
NOW MOVE the Fixed probe to the Next terminal Say “b"
Ohm reading “b” to “c” = record reading b-c
You now have three Ohm readings
a-b =
a-c =
b-c =
Now some Rules
The highest reading MUST be equal to the other two reading
ADDED together
The highest reading is a reference to two terminal (Say
“b-c”) the terminal that is not mentioned in this reference
(this case “a”) is the Common or the terminal that you connect
the Clixton or Overload to
The Second highest Ohm reading is the Run terminal
The lowest Ohm Reading is the Start Terminal
Conclusions
If the Reading DO NOT balance then the windings are burnt
between coils and compressor has to be failed
The reading must all be in the same ball park say 4.5.9
(4+5=9) or 12, 15, 27 (12+15=27) if not then the compressor is
giving false reading and must be failed.
If you really clever and are sure of your Common, Start and
Run terminals, you can try start the compressor manually by
Connecting a Neutral to the common terminal, a jumper between Run
and Start. Put power on then as the refrigeration compressor then as
the compressor labours, remove the jumper leaving Line/Live on run
and neutral on Common, the compressor should run very comfortably
(Keep a close watch on your AMPS)
Compressor Seized
If you have done all the above
tests and the compressor Passes, and still find that the
Refrigeration Compressor Amps (Current) is to high or the compressor
will not rotate then in all likelihood the compressor is seized or
failing mechanically, her are the logical symptoms
Refrigeration Compressor runs for
a short while before the clixton overload switched the compressor
off, The compressor starts up after a short while and the cycle is
repeated On /OFF (Short cycling)
The Refrigeration Compressor
merely hums and does not run
The compressor runs drawing
abnormally high current (Amps)
Compressor valves Inefficient
To test Refrigeration Compressor
Suction Valves
Disconnect all pipework from the
Hi-side / Discharge pipe of the Refrigeration Compressor
Connect your Refrigeration Gauge
Low side Gauge to the Suction /Low-side of the compressor
Open all Valves on your
Refrigeration Gauges
Start the refrigeration compressor
Close the Low side Valve on your
Gauge and observe to what level of vacuum the Refrigeration
Compressor pulls the Gauge.
A good compressor will pull the
Gauges into a deep Vacuum , A Faulty Compressor will hardly be able
to Draw a vacuum or even just get the Gauge down to Zero
To test Refrigeration Compressor
Delivery / Hi Side / Discharge Valves
Be Very Careful in Performing
this Test. Major injury and/ or Damage to equipment can Occur
Disconnect all Pipework from the
Suction / Low -side of the compressor
Connect the HIGH SIDE GAUGE of
your Refrigeration Gauges to the Hi Side / Discharge Side of the
compressor
OPEN all Valves on your
Refrigeration Gauges
Start the compressor
GENTLY close you Refrigeration
gauge Valve to throttle the Delivery of the compressor WATCH the
Gauge slowly climb as you slowly throttle the delivery
A good Compressor Discharge Valves
will very quickly MAX you Gauge out.
A Refrigeration Compressor with
burnt / bent or leaky valves will struggle to get the High side
gauge to go to its Maximum reading